How it’s calculated
- Running = Σ running watts
- Peak = running + largest (starting − running) of any one appliance
- Recommended running rating = running × (1 + margin)
Worked example
Refrigerator (700/2,200 W), space heater (1,500 W), sump pump (600/1,800 W), 20% margin.
Inputs
- Loads
- 700 × 2200; 1500 × 1500; 600 × 1800 W
- Safety margin
- 20 %
Results
- Recommended generator running rating
- 3,360 W
- Total running watts
- 2,800 W
- Peak watts (largest start)
- 4,300 W
Assumptions and limits
- Motors are started one at a time.
- Use nameplate or manufacturer data; starting watts vary widely.
Verify the result against the applicable local code, adopted code edition, manufacturer instructions and project requirements. See our methodology.
Questions
What size generator do I need to run a refrigerator?
A typical refrigerator runs at a few hundred watts but may need 1,500–2,200 W to start. Check the label or manufacturer data.
What is the difference between running and starting watts?
Running watts are continuous; starting (surge) watts are the brief peak when a motor starts.