What the animation shows
The animation and the step-by-step video above use your numbers. Here is the same walkthrough written out for the default example.

What you enter
- Conductor material: Copper.
- One-way circuit length: 100 ft. Distance from the panel to the load, not the round trip.
- Load current: 20 A.
- Voltage: 120 V.
- System: Single-phase (or DC).
- Maximum voltage drop: 3 %.
What happens, step by step
- Each bar is the voltage drop for 20 A over 100 ft one way.
- 10 AWG loses 4.14%, over the 3% limit. Try the next size.
- 8 AWG is thicker: 2.6% drop, within the 3% limit.
- 8 AWG copper is the minimum for voltage drop; also check its ampacity.
The answer: minimum size for voltage drop is 8 AWG copper.
How it’s calculated
- Required cmil = factor × K × I × L ÷ (V × max %)
- Pick the smallest standard size with at least that area
Worked example
20 A load, 100 ft one way, 120 V, copper, 3% limit.
Inputs
- Conductor material
- Copper
- One-way circuit length
- 100 ft
- Load current
- 20 A
- Voltage
- 120 V
- System
- Single-phase (or DC)
- Maximum voltage drop
- 3 %
Results
- Minimum size for voltage drop
- 8 AWG copper
- Voltage drop at that size
- 2.6%
- Voltage drop
- 3.13 V
Assumptions and limits
- Voltage drop sizing only — ampacity, temperature correction, bundling and terminal ratings are not evaluated.
- Aluminum sizes start at 12 AWG.
Verify the result against the applicable local code, adopted code edition, manufacturer instructions and project requirements. See our methodology.
Questions
What size wire for 20 amps at 100 feet?
At 120 V with a 3% limit, voltage drop alone calls for 8 AWG copper. At 240 V, 10 AWG meets 3%.
Why is this different from an ampacity chart?
Ampacity is about heating the wire safely; voltage drop is about delivering enough voltage over distance. Long runs are usually limited by voltage drop, short runs by ampacity.