How it’s calculated
- Required cmil = factor × K × I × L ÷ (V × max %)
- Pick the smallest standard size with at least that area
Worked example
20 A load, 100 ft one way, 120 V, copper, 3% limit.
Inputs
- Conductor material
- Copper
- One-way circuit length
- 100 ft
- Load current
- 20 A
- Voltage
- 120 V
- System
- Single-phase (or DC)
- Maximum voltage drop
- 3 %
Results
- Minimum size for voltage drop
- 8 AWG copper
- Voltage drop at that size
- 2.6%
- Voltage drop
- 3.13 V
Assumptions and limits
- Voltage drop sizing only — ampacity, temperature correction, bundling and terminal ratings are not evaluated.
- Aluminum sizes start at 12 AWG.
Verify the result against the applicable local code, adopted code edition, manufacturer instructions and project requirements. See our methodology.
Questions
What size wire for 20 amps at 100 feet?
At 120 V with a 3% limit, voltage drop alone calls for 8 AWG copper. At 240 V, 10 AWG meets 3%.
Why is this different from an ampacity chart?
Ampacity is about heating the wire safely; voltage drop is about delivering enough voltage over distance. Long runs are usually limited by voltage drop, short runs by ampacity.