What the animation shows
The animation and the step-by-step video above use your numbers. Here is the same walkthrough written out for the default example.

What you enter
- Convert: Watts → amps.
- Power: 1800 W.
- Voltage: 120 V.
- System: Single-phase (or DC).
- Power factor: 1.
What happens, step by step
- The load needs 1,800 W; the clamp meter reads the current it pulls.
- Amps = watts ÷ volts: 1,800 W ÷ 120 V.
- Same watts at a higher voltage means fewer amps in the wire.
- 15 A at 120 V: size the wire and breaker for that current.
The answer: current is 15 A.
How it’s calculated
- Single-phase: amps = watts ÷ (volts × PF)
- Three-phase: amps = watts ÷ (√3 × line volts × PF)
- kVA = √3 (if three-phase) × volts × amps ÷ 1,000
Worked example
An 1,800 W appliance on 120 V single-phase, power factor 1.
Inputs
- Convert
- Watts → amps
- Power
- 1800 W
- Current
- 15 A
- Voltage
- 120 V
- System
- Single-phase (or DC)
- Power factor
- 1
Results
- Current
- 15 A
- Power
- 1,800 W
- Apparent power
- 1.8 kVA
Assumptions and limits
- Three-phase uses line-to-line voltage and a balanced load.
Verify the result against the applicable local code, adopted code edition, manufacturer instructions and project requirements. See our methodology.
Questions
How many amps is 1500 watts at 120 volts?
1,500 ÷ 120 = 12.5 A for a resistive load.
How many watts can a 15 amp circuit handle?
15 A × 120 V = 1,800 W, but continuous loads (3 hours or more) are limited to 80% — 1,440 W.